Enhanced TDS
Identification & Functionality
- Chemical Family
- Industrial Additives Functions
- Technologies
- Product Families
Features & Benefits
- Industrial Additives Features
- Advantages
- Reduced build up of scale in the distribution system.
- Reduction of replacing existing piping and associated equipment attributed to excessive deposition or under-deposit corrosion.
- Assists municipalities in meeting the Lead and Copper Rule.
- NSF/ANSI Standard 60 approved for drinking water.
- Produces a tight protective coating on metal surfaces, prolonging the life of the system’s equipment.
Applications & Uses
- Markets
- Applications
- Applicable Processes
- Use Level
- max. 10 mg/l (for drinking water treatment)
- Preparation and Feeding Information
Aquacros® HC-3815 may be fed directly from the container. A dose of 10 pounds of Aquacros® HC-3815 per million gallons of water will achieve a 1.0 ppm total ortho phosphate treatment level.
Properties
- Physical Form
- Appearance
- White powder
- Typical Properties
Value Units Test Method / Conditions Poly/Ortho Blend (Dry) 15:35 Dilution (Make Down) 1.0 lbs/gal of Water - Bulk Density 41.0 lbs/ft³ - pH (at 1% Solution) 4.3 - 5.1 - - Total Phosphate 87.0 % - Phosphate Ion Content 85 - 89 %
Regulatory & Compliance
- Certifications & Compliance
- Chemical Inventories
- NSF Approval
- Aquacros® HC-3815 is approved under NSF/ANSI 60 for drinking water treatment.
Packaging & Availability
- Supplied by